From a Conduit Seal to an Explosion Relief Panel: Observing the Gap Between Taiwan’s Explosion-Proof System and International Engineering Technology
Engaging in explosion-proof engineering in Taiwan often presents a thought-provoking challenge.
Equipment is obtained with an ATEX認證 (or similar), hazardous area classification is completed, and installation contractors have completed the setup according to relevant domestic standards, sometimes even passing engineering acceptance.
But does this represent that the entire engineering project conforms to the latest international explosion-proof technical requirements?
The answer is not necessarily.
Because true explosion-proof engineering never consists merely of purchasing equipment with an explosion-proof certificate.
It also encompasses hazardous area classification, equipment selection, installation and construction, initial inspection, personnel competence, and the necessary explosion prevention and consequence protection.
As IEC 60079 standards continue to update, have Taiwan's national standards, design concepts, construction habits, and engineering management systems established synchronized updating mechanisms?
More worthy of attention is whether, while international engineering has prioritized overall explosion risk control, some projects in Taiwan remain stuck in the mindset that "as long as the equipment has an explosion-proof certificate, it is fine."
This is the issue in Taiwan's explosion-proof engineering that most deserves to be faced squarely.
I. IEC 60079-14:2024: New Version Proposes Clearer Requirements for Conduit Seal Locations
Take, for example, RSG (Rigid Steel Conduit) installation, which is common in Taiwanese factories.
Assume an Ex d 耐壓防爆控制箱 is installed within a Zone 1 explosive gas hazardous area, wired using RSG conduit, and penetrating a wall to enter a non-hazardous area.
In this scenario, where exactly should the conduit seal be installed?
Requirements of the Previous IEC 60079-14:2013
Section 9.4 of the 2013 5th edition already required that when conduits enter or leave a hazardous area, appropriate sealing devices should be installed to prevent explosive gases or liquids from migrating along the conduit into non-hazardous areas.
At the same time, the old version also restricted the installation of other fittings between the sealing device and the boundary of the hazardous area.
Therefore:
The requirement that conduits must be sealed when crossing the hazardous area boundary is not a newly added requirement in IEC 60079-14:2024.
The previous version had already established the relevant basic protection principles.
Requirements of the New IEC 60079-14:2024
On August 30, 2024, the IEC officially released the 6th edition of IEC 60079-14.
The new version re-organized the requirements for conduit systems, with Section 8.4 specifically addressing conduit systems, and Section 8.4.2 covering requirements related to Group II equipment.
Based on the organized technical information for the new conduit installation: for applicable Group II closed conduit systems:
When a conduit enters a non-hazardous area from a hazardous area, the conduit sealing device at the area boundary should be installed within the non-hazardous area.
This is what construction personnel often refer to as:
"The seal must be installed on the safe zone side."
It must be specially emphasized here that this statement has its conditions of application and cannot be directly extended to all wiring methods or all hazardous area penetration projects.
Actual construction must still be judged according to the official text of IEC 60079-14:2024, the form of the wiring system, the equipment group, and the manufacturer's installation conditions.
However, for construction training, this location requirement is highly significant.
Because construction personnel cannot just remember "it must be sealed when crossing," they must also know:
Which version of the standard is being followed? Which type of conduit system is applicable? And where should the sealing device be located?
This is the precise difference between professional international explosion-proof training and traditional experience-based construction.
II. Why might one RSG conduit line require two seals?
This is also the area where on-site misunderstandings are most likely to occur.
Under specific design conditions, a single RSG conduit may involve two different sealing requirements simultaneously.
The First: Equipment Entry Sealing
When a conduit enters Ex d 耐壓防爆 equipment, a flameproof conduit sealing device meeting requirements must be installed according to applicable standards and equipment documentation.
The purpose is to maintain the safety integrity of the connection between the flameproof enclosure and the conduit.
Taiwan's Ministry of Labor "Guidelines for the Installation of Explosion-Proof Electrical Equipment in Hazardous Areas of Business Entities" also lists the requirement that conduits entering flameproof equipment should be equipped with a sealing fitting within 50 mm of the interface.
Actual construction must still confirm the adopted standards and the manufacturer's complete regulations regarding distance, fittings, and sealing methods.
The Second: Hazardous Area Boundary Sealing
When a conduit extends from a hazardous area to a non-hazardous area, the risk of explosive gas or liquid migrating along the conduit must be evaluated separately.
For the applicable situations specified in the new IEC 60079-14:2024, this area boundary seal should be located on the non-hazardous area side.
Therefore, projects meeting relevant conditions may form the following configuration:
Hazardous Area Zone 1
Ex d Flameproof Control Box
↓
Equipment-side Flameproof Seal
↓
RSG Conduit
↓
Wall Penetration / Hazardous Area Boundary
↓
Area Boundary Seal (Non-hazardous side)
↓
Non-hazardous Area
However, this does not mean all RSG conduit lines universally require two seals, nor does it mean the area boundary sealing device must necessarily use an Ex d type.
If there is no applicable requirement for flameproof equipment entry sealing, one cannot directly deduce that equipment-side flameproof sealing must be installed.
Furthermore, the sealing of the wall penetration opening itself must also be handled according to relevant regulations such as Section 8.2.4 of IEC 60079-14:2024.
The area boundary seal inside the conduit, the equipment-side flameproof seal, and the wall penetration opening seal are three concepts that must be distinguished.
This is exactly why explosion-proof construction cannot be judged solely by experience.
III. Taiwan's Competent Authorities Have Long Acknowledged the Discrepancy Between CNS and IEC Versions
This is not a simple industry criticism, but a problem that has been explicitly pointed out by the official reasons for amendments.
Article 110 of the "Safety Standards for Machinery and Equipment" lists relevant compliance requirements for the CNS 3376 series, IEC 60079 series, or equivalent standards regarding the performance, construction, testing, marking, and hazardous area classification of gas-type explosion-proof electrical equipment.
What is even more noteworthy is that when this article was amended in 2016 (Republic of China year 105), the official reasoning clearly pointed out:
The CNS 3376 series originates from the IEC 60079 series, but the revision versions of the two cannot be synchronized, causing differences in some content, which subsequently creates confusion in compliance.
Therefore, regarding the matters regulated by this article, it is stipulated that when CNS and IEC content are inconsistent, the provisions of the IEC 60079 series shall prevail.
This illustrates an important fact:
Taiwan's competent authorities have long known that there is a difference in the update speed between national standards and international standards, and this difference may directly affect the application of technical requirements.
However, it must be noted that Article 110 mainly involves specific compliance matters such as explosion-proof electrical equipment, and it cannot be directly deduced that all construction projects necessarily only follow the latest IEC version without needing to comply with other domestic laws and regulations.
IV. Does Taiwan's explosion-proof construction guidance continue to track IEC updates?
Take CNS 3376-14 as an example.
According to the available national standard catalog information, the development date of this standard is December 5, 2002; there have been subsequent confirmation records.
However, the confirmation of a standard is not the same as a comprehensive revision of its technical content.
On the other hand, IEC 60079-14 has already undergone:
2002 Third Edition
2007 Fourth Edition
2013 Fifth Edition
2024 Sixth Edition
This time lag is worthy of continuous attention from the Taiwanese engineering community. In practical applications, one should still verify whether there are new revisions or announcements for the CNS.
In addition, the "Guidelines for the Installation of Explosion-Proof Electrical Equipment in Explosive Hazardous Areas of Business Entities," released by the Ministry of Labor in January 2024, still lists IEC 60079-14:2013 in its reference materials.
This in itself is not an error.
Because IEC 60079-14:2024 had not been officially released at that time.
But the problem is:
After the international standard was updated in August of the same year, have domestic construction education, engineering specifications, and relevant technical guidelines continuously reviewed the differences caused by the new version?
This is the true meaning of version management.
One cannot simply confirm a standard once when formulating guidelines and then ignore the continuous updates of international technology.
V. A Deeper Issue in Taiwan's Explosion-Proof Engineering: Often Neglecting Consequences After an Explosion Occurs
If we only discuss seal fittings, it is still only a part of explosion-proof electrical construction.
Another issue worthy of attention by the Taiwanese industry is explosion venting design.
Assume a factory is equipped with a combustible dust collection system.
The equipment uses explosion-proof motors suitable for hazardous areas, and the control cabinet and related electrical accessories also meet explosion-proof requirements.
However, when a combustible dust cloud forms inside the dust collector, and a deflagration is triggered by mechanical friction, electrostatic discharge, foreign object impact, or other effective ignition sources, does the equipment have adequate protective capabilities?
At this point, one needs to consider:
How much explosion pressure can the equipment enclosure withstand?
Is it necessary to install explosion venting devices?
Has the explosion venting area been calculated?
Is the explosion venting direction safe?
Will the explosion flame propagate along the dust collection ducting?
Is an explosion isolation system required?
These questions can no longer be answered solely by relying on IECEx explosion-proof electrical equipment certificates.
A qualified explosion-proof electrical equipment does not mean that the explosion risk of the entire process has been fully controlled.
This is a concept that the Taiwanese engineering community must pay more attention to.
VI. International Explosion Venting Engineering Has Long Had Complete Technical Standards
For applicable deflagration protection systems, there are already specialized international technical standards.
For example:
NFPA 68:2023
"Standard on Explosion Protection by Deflagration Venting"
It mainly proposes design, location, installation, maintenance, and usage requirements for applicable deflagration venting protection systems.
NFPA 69:2024
"Standard on Explosion Prevention Systems"
It covers applicable explosion prevention and control methods, including explosion suppression, explosion isolation, and other protective systems.
NFPA 660:2025
"Standard for Combustible Dusts and Particulate Solids"
It integrates multiple previous standards related to combustible dust, emphasizing dust hazard analysis, hazard control, equipment protection, and related safety management.
Europe also has technical standards such as EN 14491 for dust explosion venting protective systems, and EN 14994 for gas explosion venting protective systems.
These standards do not mean that all factories must install explosion venting panels.
Rather, they remind engineering designers:
When the explosion risk cannot be completely eliminated, appropriate prevention and consequence protection measures should be evaluated based on hazard characteristics.
The equipment may require explosion venting, or it may require explosion suppression, explosion resistance, explosion isolation, or other applicable engineering control methods.
The selection must have an engineering basis.
VII. Explosion Venting Cannot Be Solved by Just Installing a Rupture Panel
True explosion venting design requires understanding the explosion characteristics of the combustible material and the mechanical structure of the equipment.
Important parameters include:
Pmax: Maximum explosion pressure
Kst: Dust explosion index
Pstat: Static activation pressure of the explosion venting device
Pred: Maximum reduced explosion pressure inside the equipment after explosion venting
However, having these values does not mean that one can complete the explosion venting design on their own.
One must also consider the equipment volume, aspect ratio, combustible material characteristics, performance of the explosion venting device, structural bearing capacity, and the influence of external flames and pressure.
Especially the mechanical structure of the equipment.
If the expected maximum pressure after explosion venting still exceeds the equipment's capacity, even if the explosion venting device operates normally, the equipment may still be damaged.
In addition, if the explosion venting port faces personnel passages, operating platforms, or other important equipment, the flame and pressure generated by the deflagration may also cause surrounding harm.
For some indoor equipment, it may be necessary to evaluate flameless venting, explosion suppression, or other applicable measures.
However, these methods all have conditions of use and cannot be substituted arbitrarily.
The purpose of explosion venting engineering is not just to provide a place for equipment to release pressure, but to enable the entire protection system to have the capability to reduce the damage and personnel hazards caused by deflagration under design conditions.
At the same time, it must be noted that explosion venting is not a universal solution for all explosion or overpressure situations.
For example, detonations, runaway chemical reactions, or specific high-hazard processes all require separate evaluations for appropriate protection methods.
VIII. More Easily Overlooked Than Explosion Venting Is Explosion Isolation
Assume that a dust collection system has been equipped with appropriate explosion venting devices.
Does this mean the entire dust collection system is already safe?
Not necessarily.
Because the dust collector may be connected to multiple process equipment through ducting.
Once a deflagration occurs inside the dust collector, the flame and pressure may propagate along the ducting, further triggering secondary explosions in other equipment.
Therefore, in addition to considering explosion venting, international explosion protection engineering also attaches great importance to explosion isolation.
Applicable technologies may include verified isolation valves, fast-acting isolation systems, chemical isolation systems, and other active or passive protective devices.
These devices cannot be arbitrarily replaced by general valves.
A truly complete design does not just ask:
"Does this dust collector have explosion venting?"
But must continue to ask:
"When an explosion occurs in this dust collector, is there a way to prevent the accident from spreading to the entire process through the ducting?"
This is the mindset that overall explosion safety engineering should have.
IX. It Is Not That Taiwan Lacks Explosion Venting Guidelines, but Rather That the Actual Level of Implementation Should Be Reviewed
This point must be stated objectively.
The "Safety Precautions for Handling and Using Hazardous Substances in Factories" released by the Occupational Safety and Health Administration of the Ministry of Labor has already listed explosion venting, explosion suppression, explosion resistance, and isolation as applicable explosion protection measures.
It also mentions that NFPA 68 can be referred to for explosion venting design.
The "Guidelines for Prevention of Fire and Explosion Hazards in High-Risk Factories," released in 2025, also emphasizes hazard identification, risk assessment, and the assessment of necessary protective measures.
Therefore, it cannot be said that Taiwan completely lacks relevant technical guidelines.
What is truly worth discussing is whether these technologies have been fully implemented in engineering planning, equipment procurement, design calculations, construction, and acceptance?
When an owner purchases a set of large dust collection equipment, do they require the submission of an appropriate dust explosion hazard analysis?
Are explosion venting design calculations and equipment performance data obtained?
Does the equipment manufacturer evaluate the explosion pressure-bearing capacity of the enclosure?
Is explosion isolation required for the piping system?
Could the explosion venting flame potentially harm personnel in the vicinity?
Did the final inspection confirm that the entire protection system complies with the design conditions?
These are the questions that should be raised.
The actual implementation levels may vary across different domestic industries; it cannot be assumed that all factories have failed to implement these measures without investigative data.
However, if engineering management focuses solely on whether equipment has been purchased and construction completed, without fully verifying the design basis and effectiveness of the protection system, a safety gap may be created.
X. What Taiwan Needs Is Not Just Explosion-Proof Equipment, But Professionals with International Expertise
IEC 60079-14:2024 not only regulates the selection and installation of equipment but also includes requirements for the knowledge, skills, and competencies of designers, electrical installers, and technical personnel.
The IECEx Certificate of Personnel Competence (CoPC) system further establishes competency assessment mechanisms for different explosion-proof tasks.
For example:
Ex 001: Basic Principles of Protection in Explosive Atmospheres.
Ex 003: Installation of Explosion-Proof Equipment and Wiring Systems.
Ex 006: Testing of Electrical Installations in Explosive Atmospheres.
Ex 007: Visual and Close Inspection.
Ex 008: Detailed Inspection.
Ex 009: Design of Electrical Installations in Explosive Atmospheres.
These professional competencies are critical for explosion-proof electrical engineering.
However, systems such as explosion venting and explosion isolation also involve process safety, mechanical structure, combustion and explosion characteristics, and engineering calculations.
Therefore, the IECEx CoPC for electrical explosion protection cannot be directly regarded as a qualification for the design of all explosion protection engineering.
Different disciplines must be integrated with one another.
True explosion-proof expertise does not mean everyone must understand everything; rather, every high-risk task should be the responsibility of personnel equipped with the corresponding knowledge and competence.
XI. What Is Truly Falling Behind Is the Mentality of Waiting for Regulatory Updates Before Being Willing to Learn
International standards will not cease to develop just because Taiwan has not yet completed the revision of its national standards.
Today, the IEC updated the installation requirements for conduit systems.
Tomorrow, the NFPA may further adjust explosion protection technologies.
Future standards will also continue to be revised based on new test methods, technological developments, and lessons learned from engineering accidents.
If engineering practitioners continue to believe:
"We have always done it this way."
"The regulations do not explicitly state it."
"It is enough that the equipment has explosion-proof certification."
Then, even as international standards continue to advance, the onsite construction knowledge may remain stuck in the past.
However, new international standards should not lead to the total disregard of current local laws.
The truly correct approach is to stay abreast of the latest international technical requirements while complying with domestic regulations, and to clearly manage the scope of application and version differences between different standards.
Minimum regulatory requirements should not become the endpoint for engineering technology advancement.
XII. Youda ExTW Professional Insights: From Conduit Seals to Explosion Venting Engineering, Taiwan Must Change Its Explosion-Proof Safety Concepts
The Youda ExTW Professional Explosion-Proof and Hazardous Area Classification Training Center believes that what Taiwan truly needs to improve is not just the penetration rate of explosion-proof equipment, but the professional competence of overall explosion safety engineering.
From the requirements in IEC 60079-14:2024 regarding the boundary seal location for applicable closed conduit systems, one can see the emphasis international standards place on construction details.
From NFPA 68, NFPA 69, and NFPA 660, one can see the importance international engineering places on explosion consequences, combustible dust, and process safety management.
These technical requirements cannot be solved solely by purchasing equipment with explosion-proof certificates.
A conduit seal reflects whether the installer understands the boundaries of hazardous areas and the sealing principles of explosion-proof equipment.
An explosion venting panel reflects whether the designer understands explosion pressure, the structural strength of equipment, and the consequences of venting.
An explosion isolation system reflects whether the engineering team understands the risks of flame propagation and cascading accidents.
True explosion safety must be built on a complete engineering safety management framework, ranging from hazard identification, risk assessment, ignition source control, equipment selection, correct installation, and initial inspection, to necessary explosion venting, explosion suppression, explosion resistance, and explosion isolation.
This is also the primary reason why Youda ExTW continues to promote international explosion-proof education and training, as well as IECEx personnel competency certification.
We hope that Taiwan's explosion-proof installers will not only know how to install equipment but also understand the dangers that the standards truly aim to control.
We also hope that engineering managers can understand that obtaining explosion-proof certification for equipment does not mean that the explosion risk of the entire process has been controlled.
Taiwan's explosion-proof engineering should not wait indefinitely for national standards to be updated before starting to learn international technologies.
International standards will continue to advance, and engineering expertise must be continuously updated.
From a single conduit seal to an explosion venting panel, the true gap lies not only in equipment and construction methods but in whether one can translate international standards into correct engineering judgments and practical protection capabilities.
If one continues to use outdated construction concepts to face the explosive environmental risks of today, then no matter how much internationally certified equipment is procured, it may still be impossible to establish comprehensive explosion safety.
Explosion-proof engineering cannot be limited to doing "what the regulations require."
More importantly, it is about truly understanding risks and knowing how to control them.
This is the international integration that Taiwan's explosion-proof engineering truly needs to pursue.
Reference Materials
- IEC 60079-14:2024, 6th Edition
- Explosive atmospheres – Part 14: Electrical installations design, selection and erection, including initial inspection.
- https://webstore.iec.ch/en/publication/66049
- IEC 60079-14:2013, 5th Edition
- Explosive atmospheres — Electrical installations design, selection and erection.
- https://webstore.iec.ch/en/publication/628
- Conduits or Cables, 2026
- Compilation of conduit and cable construction techniques, including boundary sealing positions for Class II closed conduits per IEC 60079-14. This is secondary technical material; official construction compliance must be verified against the full text of the IEC standard.
- https://expeltec.com/2026/06/12/or-not-to-be-2/
- Article 110 of the "Safety Standards for Machinery and Equipment" by the Ministry of Labor
- Applicable regulations and reasoning for amendments regarding CNS 3376 and the IEC 60079 series of standards.
- https://laws.mol.gov.tw/FLAW/FLAWDOC01.aspx?flno=110&id=FL015046
- Occupational Safety and Health Administration, Ministry of Labor, 2024
- "Guidelines for the Installation of Explosion-Proof Electrical Equipment in Hazardous Areas of Industrial Establishments."
- https://laws.mol.gov.tw/FLAW/FLAWDAT0202.aspx?id=FL103010
- Bureau of Standards, Metrology and Inspection, Ministry of Economic Affairs
- Catalog of National Standards of the Republic of China (CNS), CNS 3376-14.
- https://www.bsmi.gov.tw/
- Occupational Safety and Health Administration, Ministry of Labor
- "Safety Precautions for the Handling and Use of Hazardous Substances in Factories," including explosion venting, explosion suppression, explosion resistance, and isolation measures.
- https://www.doli.taichung.gov.tw/media/1040469/工廠危險物處置使用安全注意事項.pdf
- Occupational Safety and Health Administration, Ministry of Labor, 2025
- "Guidelines for the Prevention of Fire and Explosion Hazards in High-Risk Factories," established on February 12, 2025.
- https://www.osha.gov.tw/media/pexnagjz/
- NFPA 68:2023
- Standard on Explosion Protection by Deflagration Venting.
- https://www.nfpa.org/product/nfpa-68-standard/p0068code
- NFPA 69:2024
- Standard on Explosion Prevention Systems.
- https://www.nfpa.org/codes-and-standards/nfpa-69-standard-development/69
- NFPA 660:2025
- Standard for Combustible Dusts and Particulate Solids.
- https://www.nfpa.org/
- IECEx System
- IECEx CoPC (Certificate of Personnel Competence) scheme.
- https://www.iecex.com/
ExTW Explosion-Proof Safety Joint Training Center | Explosion-Proof Professional Knowledge Base
This article is a professional discussion on explosion-proof engineering technology and standards. Actual engineering projects should be carried out in accordance with applicable laws and regulations, the full text of formal standards, equipment certificates, manufacturer documentation, and individual case risk assessments.